Y6-30-12 C-type boiler induced draft fan

Boiler Induced Draft · C-Type Drive · No. 3.5C–8.6C

Y6-30-12 Boiler Induced Draft Fan

A documented C-type induced-draft fan series for small and packaged boiler systems. The original catalogue covers seven sizes from No. 3.5C to No. 8.6C. Select by the actual airflow, total pressure, gas condition and installation interface.

Catalogue reference condition: 20°C inlet gas, 101325 Pa atmospheric pressure, gas density 0.745 kg/m³.

Y6-30-12 C-type boiler induced draft fan
655–17,262Airflow · m³/h
727–3,226Total pressure · Pa
0.75–22Motor power · kW
3.5C–8.6CDocumented model range

Documented Boiler ID Fan for Small and Packaged Boiler Systems

The original catalogue identifies Y6-30-12 for induced-draft systems on small boilers and packaged boilers. This product page carries the published model-level performance, motor, boiler-reference and installation information. The boiler-capacity values are catalogue references; final selection should use the project duty point.

Compare the Y6-30 series overview or visit the Boiler & High Temperature Fans category.

Y6-30-12 Catalogue Data

SeriesY6-30-12Model rangeNo. 3.5C–8.6C
DriveC-typeAirflow655–17,262 m³/h
Total pressure727–3,226 PaMotor power0.75–22 kW
Reference temperature20°CAtmospheric pressure101325 Pa
Gas density0.745 kg/m³Boiler reference0.2–4 t/h

Catalogue Performance by Fan Size

Use the exact model row and duty point during selection. Values below are transcribed from the published Y6-30-12 catalogue summary.

ModelSpeedTotal pressureAirflowMotorBoiler reference
3.5C2350 r/min853–727 Pa655–1,192 m³/h0.75 kW0.2 t/h
4.3C2260 r/min1206–1020 Pa1,169–2,125 m³/h1.5 kW0.2 t/h
4.8C2250 r/min1490–1265 Pa1,619–2,944 m³/h2.2 kW0.5 t/h
5.4C2300 r/min2157–1833 Pa2,202–3,963 m³/h3 kW0.5 t/h
6.5C2150 r/min2383–2020 Pa2,926–4,945 m³/h4 / 5.5 kW1 t/h
7.5C1800 / 1900 r/min2196–2736 Pa5,000–8,771 m³/h7.5 / 11 kW2 t/h
8.6C1850 r/min3226–2736 Pa9,494–17,262 m³/h18.5 / 22 kW4 t/h

Reference condition: 20°C inlet gas temperature, 101325 Pa atmospheric pressure and gas density 0.745 kg/m³. Boiler tonnage is a catalogue reference, not a substitute for airflow and pressure selection.

No. 8.6C Outline and Installation Dimensions

The available No. 8.6C catalogue drawing shows the fan outline, inlet and outlet interfaces, foundation arrangement, motor position and discharge orientations. The published page notes three drawing groups across the range; this drawing represents the No. 8.6C size.

Y6-30-12 No. 8.6C outline and installation dimensions from the catalogue
ItemCatalogue valueNote
Inlet D1 / D2 / D3510 / 566 / 616 mmInlet connection dimensions
Outlet B1 / B2 / B3 / B4430 / 220 / 536 / 332 mmOutlet connection dimensions
A4 / A5 / A61555 / 1540 / 641 mmOverall / casing-related dimensions
H1 / H21320 / 280 mmHeight-related dimensions
MotorY180M-4B3 18.5 kW / Y180L-4B3 22 kWCatalogue motor references
V-beltC/3048 × 4Catalogue transmission reference

Selection Checks for a Boiler Draft Duty

Required airflow and pressure

Confirm actual boiler exhaust airflow and the system resistance through the boiler, flue duct, dust collector, damper and chimney.

Gas condition

Provide inlet temperature, gas density, dust loading and any corrosive or abrasive condition for review.

Outlet and installation

Match the documented discharge orientation, inlet and outlet interfaces, foundation, motor rail and maintenance space to the project layout.

Motor supply

Confirm voltage and frequency for the destination market before quotation.

Typical Applications

Small boiler induced draft

The primary application stated in the catalogue.

Packaged boiler exhaust

Review within the documented airflow and pressure range.

Flue-gas cleaning systems

Include resistance from a cyclone, filter or other dust collection equipment in the duty point.

Existing fan replacement

Share the old nameplate, fan and pulley photos, motor details and installation dimensions for comparison.

Send the Boiler Duty Point

For a quotation review, share model preference, airflow, pressure, boiler capacity, inlet-gas temperature, dust condition, voltage, frequency, discharge orientation, quantity and destination. Unconfirmed engineering details can remain blank.