QIYUE FAN / SPRAY FINISHING VENTILATION
Spray Booth Exhaust Fan Selection: Define the Complete Operating Duty
A spray-booth fan quotation needs more than a booth size and motor rating. Coordinate the air supply, extraction resistance, coating process and equipment scope before comparing offers.
Supply duty
Make-up air route
Supply-filter resistance
Temperature and control
Booth duty
Workpiece and openings
Specified air distribution
Operating modes
Extract duty
Overspray separation
Duct and discharge losses
Fan construction and drive
Start with the booth designer’s airflow specification
Identify whether the project uses an open-front, cross-draft or downdraft booth, and describe the workpiece and spraying method. Ask the booth designer for the required supply and extract flows and the intended pressure relationship. Room air changes alone do not describe the airflow around the work or through the booth openings.
HSE’s guidance for isocyanate paint booths explains how supply and extraction work together to contain mist. For purchasing, translate the approved booth design into separate fan duties rather than ordering two fans with the same nominal capacity. Record the control method and who is responsible for balancing the installed system.
Compare the same filter-resistance conditions
Request the filter supplier’s flow-dependent pressure-loss data and the specified cleaning or replacement condition. Include the relevant inlet, supply treatment, overspray collection, duct and discharge losses on the correct side of the system. Keep supply-fan and extract-fan pressure schedules separate.
A clean-filter-only offer can conceal a different operating requirement from an offer based on loaded filters. Ask each supplier to show the proposed duty point and absorbed-power review for the agreed cases. OSHA’s US ventilation provisions specifically address dirty supply filters and manufacturer filter data; the project designer must establish the applicable requirements and complete pressure basis.
Specify the coating process before choosing the construction
Provide the coating and cleaning-product safety data, expected vapours or mist, temperature and the site’s hazardous-area assessment. Liquid spray finishing and powder coating are different processes and should not share an assumed fan specification.
For flammable or combustible materials, motor location, fan construction, drive arrangement and the complete ventilation system need specialist review. An explosion-protected motor alone does not establish the suitability of the fan assembly or booth. OSHA’s spray-finishing provisions include requirements for exhaust-fan motors and mechanical construction; use the rules applicable to the installation location, not a generic catalogue label.
Define what the fan supplier is actually supplying
Separate the fan and motor from the booth, filters, ductwork, controls and commissioning. If the project has spraying, purge or heated drying modes, give the designer’s airflow, temperature and control requirements for each. Do not assume a ventilation fan is suitable for a different process temperature or recirculation arrangement.
Send a coordinated quotation brief
- Process: coating system, cleaning materials, operating schedule and safety data.
- Booth: type, dimensions, openings, workpiece and designer’s airflow specification.
- Resistance: separate supply/extract schedules, filter conditions, duct layout and discharge route.
- Fan package: airflow, pressure definition, inlet temperature, construction requirements, drive, voltage and frequency.
- Interfaces: connection sizes, orientation, supports, access and responsible suppliers.
- Acceptance: fan performance documents, control checks and the booth specialist’s commissioning scope.
Keep fan acceptance and booth acceptance distinct
Check the offered fan against its specified airflow, pressure, speed and power. The installed booth also needs its own ventilation and control verification. For isocyanate spraying, HSE highlights containment and measured clearance time as part of the wider assessment. A fan curve is one input to that process, not a substitute for it.
Use the workshop ventilation guide to review make-up air, and the fan curve guide when comparing duty points. Send the approved fan duty and required construction for a project-specific review.
Technical references: HSE HSG276: managing isocyanate spray booths and rooms; OSHA 1910.94: ventilation; OSHA 1910.107: spray finishing. Refer to the applicable local requirements and the approved booth design.