QIYUE FAN · DUST EXTRACTION RETROFITS

Adding a Dust Extraction Branch: Review the Whole System Before Buying a Fan

A new machine does not automatically require a bigger fan, and an unused duct connection does not prove spare capacity. Frame the enquiry as a system change: show what is installed, what will change and which operating combinations must work after the extension.

Why an extra connection changes the review

HSE’s HSG258 explains that airflow in a multi-hood system depends on hood resistance, branch geometry and the junction with the main duct. A change to one branch affects the others. Adding hoods or closing redundant inlets can unbalance the system; reconfiguration calls for skilled rebalancing and recommissioning. Simply adjusting dampers is not a sound remedy for serious imbalance.

For procurement, this means the new hood and the existing hoods belong in the same scope. Do not accept an extension solely because air can be felt at the new connection.

Send a before-and-after change pack

1. Mark the physical change

Use two dated layouts, or one clearly marked revision. Identify the new machine, hood, branch junction, retained ducts and any removed connection. Label the collector and fan so the drawing can be matched to their nameplates.

2. Define production combinations

List the machines operating together before and after the change. Distinguish a replacement workstation from an additional simultaneous workstation. Identify future connections separately rather than silently including them in the current quotation.

3. Attach the existing evidence

Collect the installed fan curve, speed, motor information, collector data and available commissioning report. Keep measured values, original design values and proposed targets in separate columns, with the date and operating case for each.

4. Identify new process differences

Tell the responsible designer whether the new machine introduces a different material, dust characteristic, temperature or process. A matching duct diameter is not evidence that the new duty belongs on the existing collection system.

Make alternative quotations comparable

Ask for an options sheet rather than an unexplained “larger fan” price. The responsible system designer should establish the revised requirements; the fan supplier can then assess the available fan configuration against that duty.

  • Retain the fan: identify the evidence supporting the proposed arrangement and any other works included.
  • Modify the fan package: state the exact proposed changes, retained parts, revised performance data and approval responsibilities.
  • Replace the fan: compare the proposed duty, connections, controls and installation scope against the same requirements.
  • Use a separate system: keep its cost and operational assumptions visible if the project designer proposes this option.

These are quotation alternatives to evaluate, not a recommendation to alter speed, motors or ductwork. Combustible dust, incompatible materials and hazardous substances require the applicable specialist review.

Include the old hoods in acceptance

HSE’s commissioning guidance calls for proof of adequate control, performance benchmarks and correct balance at every hood. Its recommended record includes the operating conditions, test methods, results and a schematic with test points. Use that principle to agree the post-change acceptance scope before placing the order, with project-specific requirements set by the responsible competent person.

Useful purchase-order question:
“Who will demonstrate that both the new extraction point and the retained points meet the agreed performance under each specified production combination, and what records will be handed over?”

Keep the calculation and the change record together

Use the hood and branch airflow guide for the airflow basis, the filter-change retrofit guide if the collector is changing too, and the site airflow survey scope when current evidence is missing.

Return to the industrial dust collection system to review the complete air path, or compare the dust collection fan range against the revised operating point and material reaching the fan.

Planning an extraction-system extension?

Send the existing fan details, marked-up layout and revised operating requirements for a fan-package review.

Discuss the fan requirement →

References: HSE HSG258, paragraphs 270–274; HSE: Commission your LEV system. The change-pack and quotation structure above organize supplier coordination; local legal and process requirements remain project-specific.