Welding Fume Extraction Fan Selection for Multi-Station Workshops

An extraction fan for several welding stations needs a defined capture system and operating schedule. The number of welders alone is not a complete fan specification.

Two capture branches feeding a common extraction systemCapture stations A and B join a common duct leading to an air cleaner, a downstream fan and a discharge. This is a clean-side fan layout example.Station ACapture pointStation BCapture pointAir cleanerFilterFANDischargeActive branches define the operating case
Example clean-side arrangement. The LEV designer defines capture devices, filtration, fan position, discharge and replacement air for the actual workshop.

Start with the welding task and capture device

Local exhaust ventilation (LEV) captures fume near its source. On-torch extraction, extracted benches, booths and movable hoods serve different tasks. Record the welding process, workpiece size, operator movement and material or coating information so the ventilation designer can choose the capture approach.

For a movable arm, ask for its airflow and pressure requirement in the intended working position. For on-torch extraction, obtain the extraction equipment’s specified duty and connection requirements. Do not substitute a general duct fan solely because its advertised airflow is larger.

Define the operating cases before totaling airflow

Separate installed stations from stations that operate together. Give the designer the normal combination, peak combination and any planned expansion. Each case needs an agreed branch-airflow basis and a means of maintaining extraction at the active capture points.

For quotation comparison, ask each supplier to respond to the same cases. A proposal based on two active arms is not equivalent to one based on every station running. State who supplies branch controls, balancing devices, sensors and any variable-speed control, rather than assuming they are included with the fan.

Include the complete pressure path

The fan duty must account for the capture device, connecting hose or arm, duct network, air cleaner and discharge route. Obtain filter resistance for the specified operating condition, not just a clean-filter value. Avoid adding the same collector loss twice under different labels.

Confirm whether the fan receives untreated or filtered air. This affects the medium specification and construction review. The filter supplier and LEV designer should define the cleaning performance, permitted discharge or recirculation arrangement, and maintenance needs; the fan supplier needs the resulting airflow, pressure and gas condition.

A fan purchase and exposure control have different acceptance checks

The fan offer should identify its model, operating speed, airflow, pressure basis, motor and configuration. The installed LEV system also needs commissioning to verify effective capture in the real working positions. The appointed specialist should assess residual exposure and any additional protective measures. A fan curve alone does not establish that welding fume is adequately controlled.

Prepare a useful welding-extraction RFQ

  • Work: welding process, materials/coatings, workpiece geometry and operating schedule.
  • Capture: hood, arm, bench or torch interface; supplier duty data and expected working positions.
  • Stations: installed quantity and normal/peak simultaneous operating cases.
  • System: branch layout, duct lengths, filter data, fan position and final discharge.
  • Fan: design airflow and pressure, temperature, residual fume or dust, voltage, frequency and noise criterion.
  • Package: fan-only or wider supply; controls, supports, connections, documentation and commissioning responsibilities.

Connect the fan to the workshop design

Use the workshop ventilation guide to coordinate replacement air and room airflow. Use the dust collection system guide for fan location and collector interfaces. Once the extraction duty is defined, send it for a QIYUE FAN selection review.

Technical references: HSE welding fume control; HSE WL3: welding fume control; HSG258: LEV design and commissioning. Apply the requirements relevant to the project’s location and work.